MSC.1/Circ.1418 13 June 2012

GUIDELINES FOR THE DESIGN AND INSTALLATION OF A VISIBLE ELEMENT TO THE GENERAL EMERGENCY ALARM ON PASSENGER SHIPS
1 The Maritime Safety Committee, at its ninetieth session (16 to 25 May 2012), with a view to providing guidance on the addition of a visual element to the general emergency alarm system on passenger ships, as required by SOLAS regulation III/6.4.2, and following a recommendation made by the Sub-Committee on Ship Design and Equipment, at its fifty-fifth session, and the Sub-Committee on Fire Protection, at its fifty-fifth session, approved the annexed Guidelines for the design and installation of a visible element to the general emergency alarm on passenger ships.
2 Member Governments are invited to use the annexed Guidelines from 21 May 2012 when applying the relevant provisions of SOLAS regulation III/6.4.2 and to bring them to the attention of all parties concerned.
***

MSC.1/Circ.1418 Annex, page 1
I:\CIRC\MSC\01\1418.doc
ANNEX
GUIDELINES FOR A VISUAL ELEMENT TO THE GENERAL EMERGENCY ALARM SYSTEM ON PASSENGER SHIPS
1 General
This document provides guidance on the addition of a visual element to the general emergency alarm system on passenger ships, as required by SOLAS regulation III/6.4.2, for the purpose of alerting persons who are deaf or hard of hearing while minimizing the possibility of triggering seizures in persons who have photosensitive epilepsy.
2 Definitions
2.1 Effective intensity is a measure of the brightness of a flashing light equivalent to the brightness of a steady-burning light as seen by a human observer. It is determined using specialized photometric equipment and reported in candela (cd).
2.2 Field of view is the line of sight over any 135° sector from any location.
2.3 Flash rate is the number of flashes per unit of time reported in Hertz (Hz).
2.4 Illumination is the amount of light incident on a surface measured in lumens per square metre.
2.5 Photosensitive epilepsy is a chronic neurological disorder characterized by recurrent seizures triggered by visual stimuli that form patterns in time or space, such as flashing lights, bold, regular patterns, or regular moving patterns.
2.6 Polar diagram is a graph employing polar coordinates to show the variation in effective intensity as a function of direction from the visual signal device.
2.7 Public accommodation spaces are those accommodation spaces for public use by passengers, such as public spaces, dining rooms, lounges, showrooms, public restrooms, corridors, lobbies, stairways, cinemas, gymnasiums, atriums, shops, and other similar spaces. It excludes cabins and associated balconies.
2.8 Pulse duration is the time interval between initial and final points of 10 per cent of maximum intensity of the flash.
2.9 Synchronized is appearing to occur at the same time as seen by a human observer.
2.10 Visual signal is the element of the general emergency alarm conveyed by regular repeated flashes of light.
3 Principal characteristics
3.1 The general emergency alarm system in all interior public accommodation spaces should have both a visual signal and an audible signal.
3.2 The visual signal should be integrated into the general emergency alarm system such that activation of the general emergency alarm results in the concurrent activation of both audible and visual signals without further action.
MSC.1/Circ.1418 Annex, page 2
I:\CIRC\MSC\01\1418.doc
3.3 The device for producing the visual signal should have the same reliability and suitability for marine service as the other components of the general emergency alarm.
3.4 The visual signal should not interfere with the ability of the crew to safely navigate the ship at night.
3.5 The visual signal should be effective for alerting persons who are deaf or hard of hearing while minimizing the possibility of triggering seizures in passengers and crew who have photosensitive epilepsy. Visual signals with the following characteristics have been found to be acceptable*:
.1 the lamp should be a xenon strobe type or equivalent;
.2 the colour should be clear or nominal white;
.3 the effective intensity should not exceed 1,000 cd;
.4 the flash rate should not exceed two flashes per second (2 Hz) nor be less than one flash every second (1 Hz) throughout the design voltage range of the device; and
.5 the maximum pulse duration should be 0.2 s with a maximum duty cycle of 40%.
3.6 To be effective, the visual signal device should comply with Table 1. This can be verified from a polar diagram of intensity and angles determined in accordance with an international or a national standard acceptable to the Administration.**
3.7 All visual signal devices within a field of view should be synchronized. This includes strobes operated by separate systems. The field of view includes viewing from an adjacent space. However, it is not necessary to synchronize visual signal devices and other strobes located in an adjacent main vertical zone (MVZ) due to a field of view extending through a doorway or other opening in the MVZ boundary, provided that the combined flash rate of all devices and strobes in such field of view does not exceed 4 Hz.
3.8 For spaces equipped with the means of subdividing into smaller spaces (e.g. with movable bulkheads), the visual signal should be effective in each of the smaller spaces when so subdivided.
Table 1 – Minimum distribution of effective intensity Ceiling-mounted device Bulkhead-mounted device Off-angle axis (degrees) Minimum percentage of rated effective intensity Vertical distribution (degrees) Minimum percentage of rated effective intensity Horizontal distribution (degrees)
Minimum percentage of rated effective intensity 0 100% 0 100% 0 100% 45 75% 30 90% 45 75% 90 25% 90 12% 90 25%
* These characteristics are the same as found in chapter 18 of NFPA 72-2010, National Fire Alarm and Signaling Code of the United States. Devices with similar characteristics are found in many commercial and public buildings in the United States. ** An example of such a standard is ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired of the United States.
MSC.1/Circ.1418 Annex, page 3
I:\CIRC\MSC\01\1418.doc
3.9 The visual signal should be designed and installed in such a manner to be quickly noticed by an alert person anywhere within the space. Either of the approaches in 4.1 or 4.2 or an equivalent standard acceptable to the Administration is suitable.
4 System design and arrangement
4.1 Performance approach
A suitable performance requirement is complete coverage of a space with a minimum illumination of 0.4036 lumens/m2 as calculated at any point in the covered area, based on the use of the polar diagrams of the devices used.
4.2 Prescriptive approach
4.2.1 Visual signal devices should be located to provide complete coverage of the protected space.
4.2.1.1 The area of coverage of a bulkhead-mounted visual signal device is a rectangle with the device mounted halfway along one edge of the rectangle as shown in Figure 1. The maximum horizontal dimension (X) of the area of coverage for varying effective intensities is found in Table 2.
4.2.1.2 The area of coverage of a ceiling-mounted visual signal device is a square with the device located in the centre of the square as shown in Figure 1. The maximum horizontal dimension (X) of the area of coverage for varying effective intensities and lens heights is found in Table 3.
4.2.1.3 When the visual signal device is not mounted per 4.2.1.1 or 4.2.1.2, the maximum horizontal dimension (X) should be determined by doubling the distance from the device to the farthest edge of the area of coverage. The pertinent edge for a bulkhead-mounted device is the side edge, not the edge opposite the device.
Bulkhead-mounted device Ceiling-mounted device
Figure 1 – Area of coverage
X
X 0.5X
0.5X
Visual signal device
X
0.5X
MSC.1/Circ.1418 Annex, page 4
I:\CIRC\MSC\01\1418.doc
Table 2 – Maximum dimension versus effective intensity Maximum horizontal dimension (m) Minimum effective intensity (cd) 6 15 8.5 30 9 33 10 41 11 50 12 59 13 69 14 80 15 92 16 104 17 118 18 132 19 147 20 162 21 179 22 197
MSC.1/Circ.1418 Annex, page 5
I:\CIRC\MSC\01\1418.doc
Table 3 – Effective intensity of ceiling-mounted devices by maximum dimension and height of lens*** Lens height (m) 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10
Maximum horizontal dimension (m)
5 15 15 15 15 15 15 17 20 22 25 29 32 36 40 44 48 6 16 15 16 15 16 19 21 22 24 27 30 33 37 41 45 50 7 21 21 20 21 20 21 23 27 28 30 31 35 39 42 47 51 8 27 28 27 27 27 26 26 29 32 35 37 38 40 44 48 53 9 35 35 34 33 35 34 33 33 34 38 42 45 47 49 51 55 10 45 43 43 42 41 42 41 41 41 40 44 49 53 56 58 60 11 55 51 53 51 50 51 50 49 49 49 47 51 56 61 66 68 12 67 61 62 62 60 59 61 60 59 58 58 56 59 64 69 74 13 80 73 72 73 72 70 70 71 70 69 68 68 66 67 72 77 14 94 86 83 85 84 83 81 83 82 80 79 79 79 77 76 81 15 109 100 95 97 96 96 94 93 95 93 92 91 91 91 88 86 16 126 115 108 109 111 108 109 107 107 108 106 104 104 103 103 100 17 142 132 124 123 125 122 123 122 120 122 121 119 118 117 117 116 18 159 150 142 137 139 140 136 139 136 134 137 134 133 132 131 131 19 177 169 159 154 154 157 152 153 153 151 151 152 149 147 147 146 20 196 189 177 173 170 172 171 166 171 169 167 169 167 165 163 163 21 216 211 198 194 186 189 192 184 185 189 186 183 186 183 181 180 22 237 233 219 212 208 206 209 205 200 205 206 203 203 203 200 198 23 259 257 242 231 230 225 228 228 220 221 226 224 221 223 221 218 24 281 282 266 252 253 246 247 250 243 237 242 246 243 240 243 240 26 330 331 318 302 294 296 287 291 292 283 278 283 289 286 283 285
*** The effective intensities are based on providing at least 0.405 lumens/m2 at the middle of the bottom edge of the coverage area, 0.246 lumens/m2 at the bottom of the corners, and 0.243 lumens/m2 at a height of 1.5 m in the corners by a visual alarm device with the minimum distribution of effective intensities of ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired of the United States.
MSC.1/Circ.1418 Annex, page 6
I:\CIRC\MSC\01\1418.doc
4.2.2 Bulkhead-mounted visual signal devices should be mounted on the bulkhead such that the entire lens is not less than 2,030 mm and not greater than 2,440 mm above the deck surface. For spaces with multiple levels, the mounting height should be determined above the nearest deck surface.
4.2.2.1 If the bulkhead-mounted visual signal devices cannot be mounted at least 2,030 mm above the deck due to low ceiling height, the devices should be mounted within 150 mm of the ceiling. The maximum horizontal dimension (X) should be reduced by twice the difference between the actual mounting height and 2,030 mm.
4.2.3 Ceiling-mounted visual signal devices may be mounted on or suspended from the ceiling. If ceiling heights exceed 10 m, ceiling-mounted visual signal devices should be suspended at or below 10 m.
4.2.4 For corridors less than 6 m in width, the following specification may be used instead of 4.2.1.
4.2.4.1 The minimum effective intensity of the visual signal device should be 15 cd.
4.2.4.2 Visual signal devices should be located not more than 4 m from the end of the corridor with a separation not greater than 30.5 m between devices.
4.2.4.3 If there is an interruption of the concentrated viewing path, such as a fire door, an elevation change, or any other obstruction, the area should be treated as a separate corridor.
5 Testing requirements
5.1 After initial installation or modification, the system should be checked to verify proper operation including the following items:
.1 that all visual signal devices operate upon activation of the general emergency alarm system; and
.2 that all visual signal devices are synchronized as specified in 3.7.
5.2 The periodic testing of visual signal devices as part of the general emergency alarm system should be included in the maintenance plan required by SOLAS regulation II-2/14.2.2.